The T2000 Reverse Power Relay will protect the generator from being run as an electric motor. The T2000 will protect the prime mover of the generator against physical damage, but will also protect the parallel running generators from overload caused by the inversed load shift in a reverse power situation
The T2000 measures the current through an external 5A CT attached on phase L1. The phase angle (phi) is determined from the voltage measurement across L1 and L2. The T2000 calculates the active current as I x cos phi. If the active current becomes negative and exceeds the preset level (2 – 20 %), the pick-up LED will activate and the trip delay timer (2 – 20 seconds) will also activate. The built-in trip relay will energize after the delay has passed, provided that the preset trip level was continuously exceeded during the time of the delay